Error 1104

When equipment is defined at the central plant such as Boilers, Chillers, Cooling Towers and or DHW Systems (including Hydronic Heat Pumps) you must be sure to define the pump associated with that piece of equipment.

To correct this problem, go to the Plant Level of the Building Tree, and go into either the Heating Hot Water, Chilled Water, Hydronic or Domestic Hot Water tab and define the flow rate and pump power for pumps identified in this error message.