Error 1128

When modeling Closed Circuit Cooling Towers, the setpoint on the tower must be at least 10 degrees higher than the outdoor summer drybulb temperature to ensure a stable simulation.  This is a requirement of the CBECC engine.

To solve this problem, edit your Cooling Tower, and change the Setpoint Temperature input to a value that is at least 10 degrees above the Summer OADB.