CBECC performs a Cooling Tower simulation that will become unstable if the tower water DeltaT is not within specified limits.  The tower size you have specified, combined with the condenser water flow rate is outside these limits needed for the simulation.  You can either adjust the tower size (tonnage), or adjust the flow rate (gpm) to bring the resulting DeltaT with the acceptable limits of 5-20 F.